• large cooling coil in a air handling unit for a commercial building
    Mechanical HVAC Services
    Sydney and Melbourne
  • maintenance worker with spanners in a blue back ground
    Repairs and Maintenance
    Programmed, Ad-Hoc, Preventative Maintenance
  • Schematics for open plans for project construction refurbishment
    Asset Management
    Executive Services
  • HVAC Chiller
    Reduce Costs
    Energy Management Strategies and Products

Air Conditioning Services

Cooling Towers

Chemical Dosing For Cooling Towers

Remote Monitoring, with alarm parameters, can be implemented into the cooling tower water treatment and condenser water system.
Consider the following applications which we have implemented for clients in the past:

  • Alarms from the actual Chemical dosing System can be mimicked via salve relay into the Building management System
  • Monitor points via floats and switches can verify the water levels in the tower
  • Water differential pressure switches can monitor if the condenser water pumps is activated and if there is water flow
  • Water static pressure sensors can monitor the water pressure in the pipe
  • Water meter serving the “top-up” pipe can be monitored and the amount of water being used by the tower can be logged
  • These points and others can be alarmed against a given and adjustable set point

The typical dosing equipment uses 4-20milliamp outputs for Bio hazard and other measurements. These signals can be scaled and display on most Energy Management or Building Management System. “Volt Free Contacts” are often available to signal an alarm when reading are high/low or chemical is out. Simple straight forward strategies for remote monitoring of your dosing equipment.Dosing Equipment by Integra

Condenser Water Losses

Town Water “top up” Metering.
Water meter vendors often provide a pulse output to the Building Management System (BMS) or Energy Management System (EMS). Various brands provide differing levels of accuracy and price. Water meters can be provided for large pipes to serve cooling towers, town mains, and similar.

Condenser water temperatures Logged

Logging the condenser water temperatures entering and leaving the cooling tower and immediate picture of how effective the cooling tower is becomes apparent. This is ideal for considerations towards energy efficiency and also fault monitoring if the fan motors have ceased operation.

Fluid Energy Meters

Fluid energy meters can be implemented at the tower or at the equipment or data room which is using the condenser water for cooling purposes. An integer is given by the High Level Interface (HLI) of the Fluid energy meter for logging. this integer is typically in Kilo joules which is calculated by the amount of water flow through the meter and the temperature entering and leaving the system, i.e. that amount of energy which has been transferred to the condenser water system to be taken away and expelled at the cooling tower.

50mm two way fluid energy meter

Fluid Energy Meter:measure the energy lost in delivering services such as chilled water, condenser water and heating hot water

  • condenser water plant on the roof of a Parramatta Building
    Critical HVAC System Maintenance
  • natural gas pipe in a plant room to show energy source
    Effective Maintennce will Reduce Energy Costs
  • new cooling coil inside an major commercial building air handling unit
    Mechanical HVAC Services

Wraight – Technical Services in Commercial Property – Sydney and Melbourne is Stephen Fry proof thanks to caching by WP Super Cache